INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS101. PRELIMINARY INFORMATIONUNIT COOLER MODEL No.:UNIT COOLER MODEL No.:CONDENSING UNIT MODEL No
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS11REFPLUS SHALL NOT BE LIABLE:WARRANTIESRefPlus warrants the labeled (Serial No.) new RefPlus eq
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONSWI/O&M-04-04-R0-3K Printed in Canada.USA & CANADA1-888-816-26651385 De Coulomb,Bouc
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS2SAFETY CONSIDERATIONS . . . . . . . . . . . . . 3INTRODUCTION . . . . . . . . . . . . . . . . .
INSTALLATIONSTEP 1 - COMPLETE PRE-INSTALLATION CHECKSExamine for damage incurred during shipment.File a claim immediately with transit company ifdamag
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS4FAN DELAY DEFROST TERMINATION CONTROLThis control located on the coil plate senses thecoil tem
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONSDEFROST SYSTEMAIR DEFROST UNIT COOLERS: Fan motors runcontinuously and a defrost time clock or l
UNIT SPECIFICATIONSFOR ALL UNITS:- For R-134a or R-22 refrigerant charge, multiply R-404 by 1.09.- Operating charge is based on 30% liquid and 70% vap
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS7DRAIN FITTING KITAll ModelsDFK-2DEFROST CONTROLAll Models R&T G&H ETERMINAL BLOCKAll Mo
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS8TECHNICAL DATA (LS SERIES)TECHNICAL DATA (LP SERIES)Model R404A, R507 Operating Charge (lb.) Sh
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS9TECHNICAL DATA (LP SERIES)Model R404A, R507 Operating Charge (lb.) Shipping Weight (lb.)LP(G)(H